EAGLE CONTROLLER
3. Turn the rotate&push button to navigate to and highlight Alarm list.
4. Push the rotate&push button.
The ALARM LIST screen is displayed. All alarms are displayed with their
status indicator, alarm source, date, and time.
Depending on their current status, datapoints show any of the following visual
status indicators:
Icon
Function
Datapoint is in "manual mode"
Datapoint is in "Overridden status"
Datapoint is in "Alarm status"
Datapoint is in alarm status "normal"
Datapoint is in alarm status "off-normal"
Datapoint is in alarm status "low-limit"
Datapoint is in alarm status "high-limit"
Datapoint is in alarm status "fault"
NOTE:
Multiple statuses can be indicated
You can select an alarm for viewing its details and acknowledging it if
acknowledgement is required (according to the datapoint definition in CARE).
5. To do so, turn the rotate&push button to navigate to and highlight the data
point.
6. Then, push the rotate&push button.
The details of the alarm are displayed. Details include the following:
– time stamp
– alarm source
datapoint that causes the alarm
– Description
optional text entered in CARE
– alarm text
optional text entered in CARE
– alarm state transition
normal, to-off-normal, high-limit, low-limit, fault
49
BASIC OPERATION PROCEDURES
EN2Z-0971GE51 R0515