BASIC OPERATION PROCEDURES
EN2Z-0971GE51 R0515
2. Turn the rotate&push button to navigate to and highlight Schedules.
3. Push the rotate&push button. The schedule is displayed.
4. Press the softkey adjacent to the Settings command symbol
The settings of the schedule are displayed. Here you can set or edit the
default value and the valid period.
5. To edit the default value do one of the following:
a. Turn the rotate&push button to navigate to and highlight Value is
<NULL>.
b. Then, enable the option by pushing the rotate&push button.
c. Or, turn the rotate&push button to navigate to and highlight the value.
d. change the value by turning the rotate&push button
e. adjust the value by pushing the rotate&push button
NOTE:
The schedule default value is used at 00.00 (twelve midnight) as
present value of all switched properties (switch points) when no
other value is in effect. The schedule default value can be NULL
or any value, for example, ´value in %` for analog outputs, or
´running` for digital outputs. The NULL value removes the
68