AEG Protect C LCD 6000 (S) User Manual page 13

Table of Contents

Advertisement

Output overload (Bypass mode)
Voltage waveform
Harmonic distortion
Transfer time
Power factor
Load crest ratio
Output connection
Output cable
NOTE: * for 208V output, the load level will be derating to 90%.
ENVIRONMENTAL AND SAFETY
Certifications
EMC (Emissions)*
EMC (Immunity)
Agency markings
Operating temperature
Storage temperature
105-125 %: load transfers to Bypass
mode after 10 minutes
100-105 %: no alarm
105-125 %: continue working and
alarm
125-150 %: UPS shuts down after
30s
Sinewave
< 1% THDV on linear load
< 5% THDV on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms
maximum (due to loss of utility)
1
3 to 1
Hardwired
Not provided
EN 62040-1
IEC/EN 62040-2: Cat. C3
IEC/EN 62040-3
EN 60950-1
Conduction C3 IEC/EN 62040-2
Radiation C3 IEC/EN 62040-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on
signal ports), IEC 61000-4-5, Level 4,
Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
CE
0~40℃ full load no derating
40~50℃ output power derating to
50% load, Charger current derating
50%
-15 to 40°C (32 to 104°F) with
batteries
-25 to 60°C (5 to 140°F) without
batteries
13