Output overload (Bypass mode)
Voltage waveform
Harmonic distortion
Transfer time
Power factor
Load crest ratio
Output connection
Output cable
NOTE: * for 208V output, the load level will be derating to 90%.
ENVIRONMENTAL AND SAFETY
Certifications
EMC (Emissions)*
EMC (Immunity)
Agency markings
Operating temperature
Storage temperature
105-125 %: load transfers to Bypass
mode after 10 minutes
100-105 %: no alarm
105-125 %: continue working and
alarm
125-150 %: UPS shuts down after
30s
Sinewave
< 1% THDV on linear load
< 5% THDV on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms
maximum (due to loss of utility)
1
3 to 1
Hardwired
Not provided
EN 62040-1
IEC/EN 62040-2: Cat. C3
IEC/EN 62040-3
EN 60950-1
Conduction C3 IEC/EN 62040-2
Radiation C3 IEC/EN 62040-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on
signal ports), IEC 61000-4-5, Level 4,
Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
CE
0~40℃ full load no derating
40~50℃ output power derating to
50% load, Charger current derating
50%
-15 to 40°C (32 to 104°F) with
batteries
-25 to 60°C (5 to 140°F) without
batteries
13