Turn on the input breakers for the parallel UPS.
7)
Pressing
one UPS of the system, then the system will turn to line mode.
8)
Regulate the output voltage of each UPS separately, and check if
the difference of output voltage is less than 0.5V among the
parallel system. If the difference is more than 0.5V, the UPS
need to be regulated.
9)
If the difference output voltage is less than 0.5V, turn off the
input breakers to let UPS shut down. And then switch on the
output breakers for all the UPS.
10) Switch on the input breakers for the parallel UPS. Pressing
button continuously more than 1 second for one UPS of the
system, then the system will turn to line mode, after these
operations, the system will work normally in parallel mode.
Note: The output wiring requirement as below:
1)
If the distance between the UPS and breaker panel is less than
20 meters in parallel system, the length difference between
input and output cable of the UPSs is required to be less than
20%.
2)
If the distance between the UPS and breaker panel is more than
20 meters in parallel system, the length difference between
input and output cable of the UPSs is required to be less than
5%.
button continuously for more than 1 second for
61