Recommended protective devices and cable cross-sections.
Recommended upstream protection
Protect C 6000(S) LCD
Protect C 10000(S) LCD
Read the Safety instructions regarding backfeed protection requirements.
Recommended cable cross-sections
Protective earthing
conductor
Min cross section
Input L, N, G
Min conductor cross
section
Input fuse
Output L,N,
Min conductor cross
section
Battery cable*
Upstream circuit breaker
C curve, 2p63A
C curve, 2p100A
N(L2)
Protect C 6000(S) LCD
6mm
(8AWG)
2
6mm
(8AWG)
2
80A
6mm
(8AWG)
2
6mm
(8AWG)
2
to UPS Normal AC / Bypass AC
Protect C 10000(S)
LCD
10mm
(6AWG)
2
10mm
(6AWG)
2
100A
10mm
(6AWG)
2
10mm
(6AWG)
2