Testing New Batteries; Recycling The Used Equipment - AEG Protect C LCD 6000 (S) User Manual

Table of Contents

Advertisement

68
9.3.2

Testing new batteries

1.
Charge the batteries for 48 hours.
2.
By pressing
3.
Select Control then Single battery test.
The UPS can start battery test only in line mode without active alarms.
During the battery test, the UPS transfers to Battery mode and discharges
the batteries for 10 seconds. The front panel displays
percentage of the test completed.
9.4 Recycling the used
equipment
Contact your local recycling or hazardous waste center for information on
proper disposal of the used equipment.
Do not dispose of the batteries in the fire. Which may cause battery
explosion. The batteries must be rightly disposed according to local
regulation.
Do not open or destroy the batteries. Escaping electrolyte can cause injury
to the skin and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product
contains sealed, lead acid batteries and must be disposed of properly. For
more information, contact your local recycling/ reuse or hazardous waste
center.
Do not discard waste electrical or electronic equipment (WEEE) in the
trash. For proper disposal, contact your local recycling/reuse or hazardous
waste center.
The UPS is designed for durable, automatic operation and also alert you
whenever potential operating problems may occur. Usually the alarms
on the menu of "Control".