AEG Protect C LCD 6000 (S) User Manual page 12

Table of Contents

Advertisement

12
ELECTRICAL INPUT CONNECTIONS
Protect C 6000 LCD
Nominal
Over load input current (maximum
charging current, low input voltage,
continuous over load)
Protect C 6000S LCD
Nominal
Over load input current (maximum
charging current, low input voltage,
continuous over load)
Protect C 10000 LCD
Nominal
Over load input current (maximum
charging current, low input voltage,
continuous over load)
Protect C 10000S LCD
Nominal
Over load input current (maximum
charging current, low input voltage,
continuous over load)
ELECTRICAL OUTPUT
Voltage regulation
Efficiency
Frequency regulation
Nominal output
Frequency
Output overload
230V / 31.2A
Up to 43A
230V / 38.7A
Up to 53,4A
230V / 49.9A
Up to 70.1A
230V / 57.6A
Up to 79.3A
Normal mode: ±1%
Battery mode: ±1%
Normal mode:
> 98% (High Efficiency mode)
> 95%
Battery mode: > 93%
Normal mode: Sync with line ±10%
of nominal line frequency (outside
this range: ±0.1% of auto-selected
nominal frequency)
Battery mode: ±0.1% of auto-
selected nominal frequency
208V*, 220V, 230V, 240V (voltage
configurable)
6000/10000VA* 6000/10000W*
50 or 60Hz, autosensing or
configurable as a frequency
converter
100-105 %: no alarm