3.25 ASSEMBLING THE MANIFOLD ON THE CONDENSATION MODULE
1. Place the manifold (2, Fig. 66 or Fig. 67) on the module (3, Fig. 66 or Fig. 67).
2. Tighten the 4 nuts (1, Fig. 66 or Fig. 67) on the condensation module (3, Fig. 66 or Fig. 67) in the sequence (A, B, C, D of Fig. 66 or Fig. 67)
shown in the drawing.
The tightening torque when assembling the manifold (2) on the condensation module (3) must be 4 Nm.
Do not exceed 5 Nm.
Victrix Tera V2 28 EU - V2 32 EU
Victrix Tera V2 38 EU
A
1
D
A
1
D
C
B
C
B
3
2
1
3
2
1
66
67
89