Appliance Switch-Off; Restore Central Heating System Pressure; Draining The System; Emptying The D.h.w. Circuit - Immergas Victrix Tera V228 EU Manual

Table of Contents

Advertisement

2.7

APPLIANCE SWITCH-OFF

Switch the appliance off by putting it in "off" mode, disconnect the main switch outside of the appliance and close the gas cock upstream
of the appliance.
Never leave the appliance switched on if left unused for prolonged periods.

2.8 RESTORE CENTRAL HEATING SYSTEM PRESSURE

1. Periodically check the system water pressure (the appliance's pressure gauge hand must indicate a cold value between 1 and 1.2 bar).
2. If the pressure is below 1 bar (with the circuit cool), restore normal pressure from the relative cock (Part. 1, Fig. 7).
3. Close the cock after the operation.
4. If the pressure rises to values close to 3 bar, there is a risk of the safety valve tripping (in this case, remove water from an air release
valve on a radiator or by acting on the drain valve (Det. 2, Fig. 7) until the pressure is restored to 1 bar, or call in professionally qualified
personnel).
If the system is hot, be sure to let it cool down before draining to avoid the risk of scalding.
5. In the event of frequent pressure drops, contact qualified staff for assistance to eliminate the possible system leakage.
2.9

DRAINING THE SYSTEM

To drain the boiler, use the special draining valve (Part. 2, Fig. 7).
Before draining, ensure that the filling cock is closed.
If fluid containing glycol was added to the system circuit, make sure it is recovered and disposed of in accordance with standard
EN 1717.

2.10 EMPTYING THE D.H.W. CIRCUIT

To do this, always close the domestic cold water inlet upstream of the appliance.
Open any domestic hot water tap to discharge the pressure from the circuit.
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Victrix tera v232 euVictrix tera v238 eu

Table of Contents