Parameter
Parameter
t8
Display
Flow off
t9
temperature
increase
Id
Parameter
Parameter
Hydraulic
A0
model
Maximum
A1
pump speed
Minimum
A2
pump speed
Circulating
A3
pump mode
Storage tank
A4
flow offset
Storage tank
A5
activation offset
D.H.W.
A6
thermostat
Description
Establishes what the indicator displays (Fig. 39).
"Summer" mode:
0: the indicator is always off.
1: pump active displays the flow temperature, pump off the
indicator is off.
"Winter" mode:
0: it always displays the value set on the central heating
selector.
1: circulator pump active displays the flow temperature,
pump off displays the value set on the central heating
selector.
Increases the flow off temperature at ignition only in the first
60 seconds. After the flame is detected, the temperature is
increased by t9.
Description
Defines the type of hydraulics in the boiler (0 = instant; 1 =
storage tank).
Defines the maximum operating speed of the circulator (If
A1 = A2 circulator operating at set speed).
Defines the minimum operating speed of the circulator.
Sets the pump operating mode
DELTA T = 0: proportional head (Par.. 1.29).
- DELTA T = 5 - 25 K: ∆T constant (Par.. 1.29)
Not available for this model
Not available for this model
Establishes the switch-off method in DHW mode.
0 Fixed: the switch-off temperature is fixed at the maximum
value regardless of the value set on the control panel.
1 Correlated: the boiler switches off according to the
temperature set.
Range
Default
0 - 1
1
0 - 15
0
Range
Default
0 ÷ 1
0
A2 - 9
9
1 - A1
6
0 ÷ 25
15
-
-
-
-
0 ÷ 1
0
Customised
value
Customised
value
75