NOTE!
Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS's maximum input current. The receptacle
may be damaged and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
Ranger 60KR
NOTE 1: The cable for Ranger 60KR should be able to withstand over
120A current. It is recommended to use AWG 4 or thicker wire for Phase
and AWG 1 or thicker wire for Neutral for safety and efficiency.
NOTE 2: The selections for color of wires should be followed by the local
electrical laws and regulations.
5) Remove the terminal block cover at the rear panel of UPS. Then connect
the wires according to the following terminal block diagrams: (Connect
the grounding/earthing wire first when making other wire connections.
Remove the grounding/earthing wire last when connecting the UPS!)
Terminal block wiring diagram for Ranger 60KR
8
Input(Ph)
Output(Ph)
4
4
Wiring spec (AWG)
Neutral
Battery
1
1
Ground
4