15: Inverter A voltage adjustment
Interface
Parameter 2: you may choose Add or Sub to adjust inverter A voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the default value
Setting
is 0V.
* Add or Sub is according to the output voltage what you set.
16: Inverter B voltage adjustment
Interface
Parameter 2: you may choose Add or Sub to adjust inverter A voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the default value
Setting
is 0V.
*It will display number 1 under
voltage.
17: Inverter C voltage adjustment
Interface
Parameter 2: you may choose Add or Sub to adjust inverter C voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default value
Setting
is 0V.
*It will display number 2 under
voltage.
18: Output A voltage calibration
Interface
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output
A voltage, and you can calibrate it by pressing Up or Down according
Setting
to the measurement from an external voltage meter. The calibration
result will be effective by pressing Enter. The calibration range is limited
within +/-9V. This function is normally used for parallel operation.
or
to represent inverter B
or
to represent inverter C
31