Analog Set Point (Apc) - ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

3.4.8.4.
32
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Data Class Spe-
cific
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Send All Updates
True
False
Default: False
Send As Double
True
Point
False
Default: False
Send As Inverse
True
Value
False
Default: False
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time

Analog set point (APC)

Table 3.4.8.4-1 Configurable APC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
APC
Class
Addresses
Control Index
-1...65535
Default: -1
Description
Object number for indication.
Defines if all changes in value are sent to
the master.
Defines if a value is sent as double point.
Defines if the value of a message is
inverse.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC
61850.
Control index.
1MRS756567