Analogue Set Point (Apc) - ABB COM600 series User Manual

Modbus serial slave (opc)
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS756913
3.4.5.4.
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Update Rate
0...60000
Default: 0
Data Specific
Send as Double
True
Point
False
Default: False
Send as Inverse
True
Value
False
Default: False

Analogue set point (APC)

Table 3.4.5.4-1 Configurable APC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
APC
Class
Addresses
Control Address
0...65535
Default: 0
Indication Address
0...65535
Default: 0
Description
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Specifies if a value of an indication signal
is sent as a double point value.
Specifies if a value of an indication signal
is sent as an inverse value.
Description
Common data class according to IEC
61850.
Control address. Holding register address
for the control. Holding register (4X refer-
ence) address range 40001-49999.
Address 0 equals no information available.
Indication address. Holding register
address for the control. Holding register
(4X reference) address range 40001-
49999. Address 0 equals no information
available.
27

Advertisement

Table of Contents
loading

Table of Contents