Level 9 - Set Point Configuration - ABB COMMANDER C355 User Manual

Commander 350 series controlit 1/4 din advanced process controller
Table of Contents

Advertisement

...5.5 Level 9 – Set Point Configuration
•1
9. . 0 6
SP. F A
NONE
•1
9. . 0 7
dF. S P
0. 0
9. . 0 8
L. S r1
NONE
9. . 0 9
L. S r2
NONE
9. 1 0
L. S r3
NONE
9. 1 1
L. S r4
NONE
•1
Displayed only if a remote set point template is selected.
•2
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
Remote Set Point Fault Action
The action required when a fault occurs with the remote set point.
No action
NONE
Select local set point mode
LOC
Select local set point mode and set to the default value
dFLt
Local Set Point Default Value
Set the value required for the local set point under remote set point fault
conditions.
[In engineering units]
Local Set Point Source 1
The source required to select local set point 1 (LSP1) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Local Set Point Source 2
The source required to select local set point 2 (LSP2) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Local Set Point Source 3
The source required to select local set point 3 (LSP3) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Local Set Point Source 4
The source required to select local set point 4 (LSP4) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Continued...
5 CONFIGURATION MODE...
9.06...9.11
LSP1
•2
LSP2
•2
•2
LSP3
LSP4
•2
81