Parameter
Name
Energy saving monitor reference
893
(motor capacity)
Frequency setting voltage gain
C24(923)
frequency (built-in potentiometer)
When Pr.80 Motor capacity  "9999," the Pr.80 Motor capacity setting is not changed by IPM parameter initialization. IPM parameter initialization is performed
by setting Pr.998 IPM parameter initialization or the parameter setting mode on the operation panel.
REMARKS
 If IPM parameter initialization is performed in rotations per minute (Pr. 998 = "1"), the frequency-related parameters not listed in
the table above and the monitored items are also set and displayed in rotations per minute.
 The Pr. 998 setting automatically changes the Pr. 71 setting but does not change Pr. 0 Torque boost and Pr. 12 DC injection brake
operation voltage settings.
<IPM motor specification list>
Rated motor frequency
(rotations per minute)
Maximum motor frequency
(rotations per minute)
Minimum frequency
(rotations per minute)
Specification comparison with the general-purpose motor
Item
Applicable motor
Number of connectable
motors
Number of motor poles
Rated motor frequency
Maximum output
frequency
Permissible load
Maximum starting
torque
Frequency
Analog
setting
input
resolution
Pulse
Output
output for
signal
meter
Carrier frequency
79
General-purpose
motor
0
Pr.998
(Initial setting)
Rated inverter capacity
60Hz
MM-EF
MM-EFS
90Hz (1800 r/min)
75Hz (1500 r/min)
135Hz (2700 r/min)
112.5Hz (2250 r/min)
9Hz (180 r/min)
7.5Hz (150 r/min)
IPM motor control
Premium high-efficiency IPM motor MM-EFS series
(the same capacity as the inverter capacity)
1: 1
6 poles
75Hz
112.5Hz (6P 2250r/min)
120% 60s, 150% 0.5s (inverse-time characteristics)
(The % value is a ratio to the rated motor current.)
50%
0.018Hz/0 to 75Hz (1500r/min)
(0 to 10V / 12 bits)
0.036Hz/0 to 75Hz (1500r/min)
(0 to 5V / 11 bits, 0 to 20mA / 11 bits, 0 to 10V /
12 bits)
0.072Hz/0 to 75Hz (1500r/min)
(0 to 5V / 11 bits)
In the initial setting, 1mA is output at 75Hz from
across terminals FM and SD. (SD is a common
terminal.)
The permissible frequency load current is 2mA.
For pulse specification, 1440 pulses/s is output at
75Hz.
five patterns of 2.5kHz, 5kHz, 7.5kHz, 10kHz and
12.5kHz
Setting
IPM motor
IPM motor
(rotations per
(frequency)
minute)
1 (MM-EF),
101 (MM-EF),
12 (MM-EFS)
112 (MM-EFS)
Motor capacity (Pr.80)
Rated motor
Rated motor
rotations per minute
frequency
General-purpose motor control
General-purpose motor SF-JR, HR series, etc.
(the same or one-rank higher capacity compared to
the inverter)
Several motors can be driven under V/F control.
Normally 2, 4, or 6 poles.
Normally 50Hz or 60Hz
400Hz (12000r/min with 4P) (Set the upper limit
frequency (Pr.1, Pr.18) according to the motor and
machine specifications.)
120% 60s, 150% 0.5s (inverse-time characteristics)
(The % value is a ratio to the rated inverter current.)
120% (General-purpose magnetic flux vector control)
0.015Hz/0 to 60Hz (1800r/min with 4P)
(0 to 10V / 12 bits)
0.03Hz/0 to 60Hz (1800r/min with 4P)
(0 to 5V / 11 bits, 0 to 20mA / 11 bits, 0 to 10V /
12 bits)
0.06Hz/0 to 60Hz (1800r/min with 4P)
(0 to 5V / 11 bits)
In the initial setting, 1mA is output at 60Hz from
across terminals FM and SD.
(SD is a common terminal.)
The permissible frequency load current is 2mA.
For pulse specification, 1440 pulses/s is output at
60Hz.
0.75kHz to 14.5kHz
Setting increments
1, 12
0, 101, 112
0.01kW
1 r/min
0.01Hz