13
Minimum motor rotation frequency
IPM
IPM
IPM
Pr.13 Starting frequency
Set the frequency where the motor starts running.
Set the deadband in the low-speed range to eliminate noise and
offset deviation when setting a frequency with analog input.
Output
frequency
(Hz)
60
Set
frequency
Setting
range
Pr. 13
0
Forward rotation
∗ Output from 0.01Hz
14
V/F pattern matching applications
V/F
V/F
V/F
Pr.14 Load pattern selection
You can select the optimum output characteristic (V/F characteristic)
for the application and load characteristics.
Enabled only under V/F control.
For constant-torque load (setting "0")
Pr. 14 = 0
 At or less than the base
100%
 Set this value when driving the
Pr. 3 Base frequency
Output frequency (Hz)
For variable-torque load (setting "1",
Pr. 14 = 1
initial value)
 At or less than the base
100%
 Set this value when driving the
Pr. 3 Base frequency
Output frequency (Hz)
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Output
frequency
Time
ON
frequency voltage, the output
voltage varies linearly with the
output frequency.
load whose load torque is
constant if the speed varies, e.g.
conveyor, cart or roll drive.
frequency voltage, the output
voltage varies with the output
frequency in a square curve.
load whose load torque varies in
proportion to the square of the
speed, e.g. fan or pump.
15, 16
Jog operation
Pr.15 Jog frequency
You can set the frequency and acceleration/decelertion time for
jog operation. Jog operation can be performed from either the
outside or PU.
Can be used for conveyor positioning, test operation, etc.
Output frequency (Hz)
Pr. 20
Pr. 15 Jog frequency
Forward
rotation
setting range
Pr. 16
JOG signal
Forward rotation STF
ON
Reverse rotation STR
17
Logic selection of output stop signal
(MRS)
Pr.17 MRS input selection
The inverter output can be shut off by the MRS signal. The logic of
the MRS signal can also be selected.
When
Pr. 17
is set to "4", the MRS signal from external terminal
(output stop) can be changed to the normally closed (NC contact)
input, and the MRS signal from communication can be changed to
the normally open (NO contact) input.
The motor coasts to stop
Time
ON
MRS signal
STF (STR)
ON
signal
18
Refer to the section about Pr.1
19
Refer to the section about Pr.3
20
Refer to the section about Pr.7
Pr.16 Jog acceleration/deceleration time
Reverse
Time
rotation
ON
ON
Setting value "0"
(initial value)
Setting value "2"
Inverter
Inverter
Output stop
Output stop
MRS
MRS
SD
SD
32