Mitsubishi Electric FR-700PJ Manual page 47

Advertisement

338, 339, 551
Operation command source and speed
command source during
communication operation
Pr.338 Communication operation command source
Pr.339 Communication speed command source
Pr.551 PU mode operation command source selection
When the RS-485 communication with the PU connector is used,
the external start command and frequency command can be valid.
Command source in the PU operation mode can be selected.
Pr.
Setting
Number
Range
0 (initial
Start command source communication
value)
338
1
Start command source external
0
(initial
Frequency command source communication
value)
1
Frequency command source external
339
Frequency command source external
(Frequency command from communication is
2
valid, frequency command from terminal 2 is
invalid)
PU connector is the command source when PU
2
operation mode.
Operation panel is the command source when
4
PU operation mode.
551
Parameter unit automatic recognition
9999
Normally, operation panel is the command
(initial
source. When the parameter unit is connected to
value)
the PU connector, PU is the command source.
 Pr. 551 is always write-enabled.
340
Refer to the section about Pr.79
342, 343
Refer to the section about Pr.117
450
Refer to the section about Pr.71
374
Overspeed detection
Pr.374 Overspeed detection level
Inverter outputs are stopped when the motor speed exceeds the
Pr.374 Overspeed detection level under IPM motor control.
Pr.374
Setting
When the motor speed exceeds the speed set in Pr.374,
0 to 400Hz
overspeed (E.OS) occurs, and the inverter outputs are
stopped.
9999
No function
(initial value)
Motor speed
Pr. 374
ALM
49
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Description
IPM
IPM
IPM
Description
Coast to stop
Time
ON
E.OS
495, 496
Remote output function (REM signal)
Pr.495 Remote output selection
You can utilize the ON/OFF of the inverter's output signals instead
of the remote output terminal of the programmable controller.
Pr.
Setting
Number
Range
0
Remote output data clear
(initial
at powering OFF
value)
Remote output data
1
retention even at powering
OFF
495
Remote output data clear
10
at powering OFF
Remote output data
11
retention even at powering
OFF
496
0 to 4095
Refer to the following diagram.
 This parameter allows its setting to be changed during operation in any
operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
<Remote output data>
Pr.496
b11
 As desired (Always "0" during reading)
502
Refer to the section about Pr.117
503, 504
Part maintenance
Pr.503 Maintenance timer
Pr.504 Maintenance timer alarm output set time
When the cumulative energization time of the inverter reaches the
parameter set time, the maintenance timer output signal (Y95) is
output.
(MT) is displayed on the operation panel.
This can be used as a guideline for the maintenance time of
peripheral devices.
First power
ON
9998
(999800h)
Set "0" in Pr. 503
Maintenance
timer
Pr. 504
(Pr. 503)
Y95 signal
OFF
ON
MT display
The cumulative energization time of the inverter is stored into the
EEPROM every hour and indicated in Pr. 503 Maintenance timer in
100h increments. Pr. 503 is clamped at 9998 (999800h)
.
Refer to the section about Pr.117
549
Refer to the section about Pr.338
551
Refer to the section about Pr.127
553, 554
Pr.496 Remote output data 1
Description
Remote output
data is cleared
during an inverter
reset
Remote output
data is retained
during an inverter
reset
b0
Time
ON