Wire and Space Saving
(1) A lineup of Filterpack models available
•The power factor improving DC reactor, common mode choke (line
noise filter), and capacitive filter (radio noise filter) are all essential for air
conditioning applications, and all of these are included in a Filterpack.
The Filterpack inverter models (FR-F70PJ-F) are also available. The
option wiring, which was necessary in the past, is no longer required.
Common
Power
mode choke
supply
Flexible
Capacitive filter
installation
(radio noise filter)
M
Power factor improving
DC reactor
Motor
Filterpack
(2) Space saving by the side-by-side installation
•Side-by-side installation is
possible*
and requires less space.
2
A DIN rail installation attachment (FR-UDA) option can be installed.
*2: Keep the surrounding air temperature of the inverter at 40 °C maximum.
Side-by-side installation is not available for Filterpacks.
Easy Operation and Maintenance
(1) Quick setting using the setting dial
•The adaptable scroll speed setting dial
allows for quick jumps or precise
increments based on turning speed.
•The non-slip treatment was applied to the
setting dial for easier turning.
(2) Automatic parameter setting for speci c applications
•Simple parameter setting (Pr.79 Operation mode selection)
•Communication setting for Mitsubishi HMI (GOT)
•Rated frequency change (60Hz → 50Hz)
(3) Spring clamp terminals
(control circuit terminals)
Spring clamp
terminals*
1
are adopted as control circuit terminals.
Spring clamp terminals are highly reliable and can be easily wired.
*1: The control circuit terminals are screw terminals.
Tensile strength
conforming to the
DIN standard
Easy wiring
only by inserting
wires
Introducing the
•Offers a selection of small frames
Mitsubishi magnetic
3
•Offers a line-up of safety contactors
contactor
•A Filterpack allows flexible installation and various layouts in the
enclosure. Smaller space is required for installation.
•Less wiring and smaller space also enable compliance with the Harmonic
Suppression Guidelines, the Architectural Standard Specifications
(Electrical Installation), and the Architectural Standard Specifications
(Machinery Installation) (2013 revisions) in Japan.
Installation area
Back of the panel
Side of the panel
reduced
by*
1
Approx.
72%
Filterpack
Filterpack
With
FR-F740PJ-3.7KF
Power
Power
Motor
Motor
M
M
supply
supply
*1: The area required for the separate installation of power factor improving DC reactor, common mode
choke (line noise filter), and capacitive filter (radio noise filter) with clearance around them.
(4) Longer life parts
•The service life of the cooling fans is now 10
years*
can be further extended by ON/OFF control of the cooling fan.
•Capacitors with a design life of 10
years*
2
*
3
are adapted.
(Surrounding air temperature of 105ºC for 5000 hours). With these
capacitors, the service life of the inverter is further extended.
*2: Surrounding air temperature: Annual average of 40ºC (free from corrosive gas, flammable
gas, oil mist, dust and dirt). The design life is a calculated value and is not a guaranteed
product life.
*3: Output current: 80% of the inverter rating.
(5) The leading-edge life diagnosis function
•The degree of deterioration of the main circuit capacitor, control
circuit capacitor, and inrush current limit circuit
can be diagnosed on the monitor.
•Using the self-diagnosis function, the part life
warning*
4
can be output. With these warnings, the self-diagnosis
function prevents troubles from occurring.
*4: A warning is output when any of the main circuit capacitor, control circuit
capacitor, inrush current limit circuit, and cooling fan reaches its specified output level.
(6) Enhanced communication function
•The Mitsubishi inverter protocol and Modbus-RTU are selectable.
•The speed of RS-485 communication has been improved.
(Communication at 38.4kbps is available.)
•Supports small loads (auxiliary contact)
•Supports many international regulations as standard
Optimum for Fan and Pump Applications
(1) Enhanced PID control
•To save energy in low-speed operation: PID output shutoff (sleep) function
•To shorten the start-up time of PID control: PID automatic switchover function
•For air conditioning applications: Forward/reverse rotation switching
•To use various types of detectors: PID set point and measured value
Installation area
reduced
by*
1
Approx.
84%
(2) Regeneration avoidance function
With
FR-F740PJ-3.7KF
200 mm or less
depth at all capacities
The operation frequency is automatically increased to prevent the
regenerative overvoltage fault from occurring. This function is useful
when a load is forcibly rotated by another fan in the duct.
Example
The fan is rotated by the external force.
We need smooth start-up
2
. The service life
flying start function.
The motor can be started smoothly even after the motor was
rotated by the external force (coasting).
This function can be set enabled by changing
Power supply
Motor
speed
Output
frequency
Without the function
Parameters to adjust the acceleration time at a restart (Pr.611), to
detect the fan rotation direction (Pr.299), etc. are also available.
Refer to page 65
for the selection.
(3) Automatic restart after instantaneous power
failure function / ying start function
After an instantaneous power failure, the operation is re-startable from
the coasting motor speed.
by external signals
Even if the rotation direction has been forcibly reversed, the operation
can be smoothly restarted in the original direction.
outputs in voltage (0 to 5V / 0 to 10V)
and current (4 to 20mA)
(Example: Water-cooling pump for a showcase)
of the motor.
Use the
regeneration avoidance function.
When the external force accelerates rotation of the running motor
(regeneration), the motor may trip due to the overvoltage.
Pr.57
setting.
The regeneration avoidance function is available to increase the
frequency and avoid the regenerative condition.
Power supply
Sudden change
Smooth
This function can be set enabled by changing
of rotation
starting
Motor
speed
Motor
speed
Output
frequency
Bus voltage
With the function
Output
frequency
Without the function
Parameters to start the regeneration avoidance operation (Pr.883)
and to adjust the response level (Pr.886) are also available.
Coasts during
instantaneous
power failure
We need continuous operations
without being interrupted by the
overvoltage protective function
(E.OV).
Use the
Pr.822
setting.
Motor
speed
OV trip
The trip does not occur and
the operation continues.
Bus voltage
Output
frequency
With the function
4