Download Print this page

Mitsubishi Electric FR-700PJ Manual page 43

Advertisement

161, 295
Operation selection of the operation
panel
Pr.161 Frequency setting/key lock operation selection
Pr.295 Magnitude of frequency change setting
 You can use the setting dial of the operation panel like a
potentiometer to perform operation.
 The key operation of the operation panel can be disabled.
Pr.161
setting
0
Setting dial frequency setting mode
(initial value)
1
Setting dial potentiometer mode
10
Setting dial frequency setting mode
11
Setting dial potentiometer mode
 When setting a frequency using the setting dial on the operation
panel, the frequency change increment is determined by how
quickly the setting dial is rotated.
Refer to the section about Pr.57
162, 165
Refer to the section about Pr.150
166 ,167
Parameter for manufacturer setting. Do not set.
168, 169
Refer to the section about Pr.52
170, 171
45
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Description
Key lock mode in valid
Key lock mode valid
178 to 182
Function assignment of input terminal
Pr.178 STF terminal function selection
Pr.180 AU terminal function selection
Pr.182 RH terminal function selection
Use these parameters to select/change the input terminal
functions.
Pr.178 to
Signal
Pr.182
Name
setting
Pr.59 =0 (initial value)
0
RL
Pr.59  0 
Pr.59 =0 (initial value)
1
RM
Pr.59  0 
Pr.59 =0 (initial value)
2
RH
Pr.59  0 
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
External thermal relay input 
7
OH
15-speed selection (combination with three
8
REX
speeds RL, RM, RH)
Inverter run enable signal (FR-HC2, FR-CV
10
X10
connection)
12
X12
PU operation external interlock
14
X14
PID control valid terminal
PU/External operation switchover (turning ON
16
X16
X16 selects External operation)
24
MRS
Output stop
25
STOP
Start self-holding selection
Forward rotation command (assigned to STF
60
STF
terminal (Pr. 178) only)
Reverse rotation command (assigned to STR
61
STR
terminal (Pr. 179) only)
62
RES
Inverter reset
64
X64
Starting frequency for elevator mode
65
X65
PU/NET operation switchover
66
X66
External/NET operation switchover
67
X67
Command source switchover
72
X72
PWM frequency selection
9999
No function
 When Pr. 59 Remote function selection  "0", the functions of the RL, RM
and RH signals are changed as given in the table.
 The OH signal turns ON when the relay contact "opens".
Pr.179 STR terminal function selection
Pr.181 RM terminal function selection
Function
Low-speed operation
command
Remote setting (setting
clear)
Middle-speed operation
command
Remote setting
(deceleration)
High-speed operation
command
Remote setting
(acceleration)