 Enables continuous regenerative operation at 100% torque. This option can support continuous regenerative operations including line operation.
 This converter eliminates the need of preparing brake units per inverter. This converter can cut down the total space and the cost.
 The regenerated energy is used by another inverter, and if there is still an excess, it is returned to the power supply, saving on the energy
consumption.
 The exothermic section of the heatsink protrusion type protrudes from the back side of the enclosure to dissipate the heat generated from the
converter to the outside of the enclosure.
 Connection diagram
MCCB
Three-phase
AC power
supply
Power regeneration
common converter
(Note) A Filterpack cannot be connected when FR-CV is connected.
FR-CV-(H)

K
 Outline dimension
W

FR-CV type
Dedicated stand-alone
Power regeneration
reactor (FR-CVL)
common converter
MC
1
R/L
R2/L
11
12
R2/L
1
S/L
21
S2/L
22
S2/L
2
T/L
31
T2/L
32
T2/L
3
R/L
11

S/L
21
T/MC1
[FR-CV-(H)-AT]
[FR-CV-(H)]
H
D1
D1
W
D
D
[FR-CVL]
D
H
W
Specification and Structure
 Do not connect anything to power input terminals (R/L1,
S/L2, T/L3). Incorrect connection will damage the
R/L1
U
inverter.

S/L2
V
M
T/L3
Connecting the opposite polarity of terminals N/- and P/
W
+ will damage the inverter.
 Do not insert an MCCB between the terminals P/+ and
N/- (between terminals P/L+ and P/+ or between N/L- and
Inverter
N/-).

P/L+
P/+
Always match the terminal symbols (P/+, N/-) at the
N/-
N/L-
inverter side and at the power regeneration common
P24
PC
converter side. Incorrect connection will damage the
SD
SD
inverter.
RDYA


Do not remove the jumper across P/+ and P1.
RDYB
X10
RSO
RES
 Be sure to connect the power supply and terminals R/
SE
SD
L11, S/L21, and T/MC1. Operating the inverter without
connecting them will damage the power regeneration
common converter.
 Install the dedicated stand-alone reactor (FR-CVL) on a
horizontal place.
 Assign the terminal for X10, RES signal using any of Pr.
178 to Pr. 182 (input terminal function selection).
 Always connect terminal RDYB of the FR-CV to an
inverter terminal where the X10 signal or the MRS
signal is assigned to. Always connect terminal SE of the
FR-CV to the inverter terminal SD. Not connecting these
terminals may damage the FR-CV.
FR-CV-(H)
Voltage/capacity
W
H
7.5K/11K
90
300 303 103
15K
120 300 305 105
22K/30K
150 380 322 122
H
37K/55K
400 620 250 135
FR-CV-(H)-AT
Voltage/capacity
W
H
7.5K/11K
110 330 315 115
15K
130 330 320 120
22K/30K
160 410 350 150
FR-CVL
Voltage/capacity
W
H
7.5K/11K/
165 155 130
15K
22K
165 155 140
30K
215 175 160
37K
220 200 320
55K
250 225 335
(unit mm)
D
D1 Voltage/capacity
W
H
D
7.5K/11K/
120 300 305 105
15K
22K/30K
150 380 305 105
37K/55K
400 620 250 135
D
D1 Voltage/capacity W
H
D
7.5K/11K/
130 330 320 120
15K
22K/30K
160 410 350 150
(unit mm)
D
Voltage/capacity
W
H
D
7.5K/11K
220 200 135
15K
220 205 135
22K
220 215 150
30K
245 220 185
37K
245 265 230
55K
290 280 230
D1
(unit mm)
D1
62