PU contrast adjustment
Pr.991 PU contrast adjustment
Contrast adjustment of the LCD of the parameter unit (FR-PU04/
FR-PU07) can be performed.
Decreasing the setting value makes the contrast lighter.
Pr.991 setting
0 to 63
997
Initiating a fault
Pr.997 Fault initiation
A fault is initiated by setting the parameter.
This function is useful to check how the system operates at a fault.
The read value is always "9999." Setting "9999" does not initiate a
fault.
 Setting for Pr.997 Fault initiation and corresponding faults
Pr.997
Pr.997
Fault
setting
setting
16
E.OC1
17
E.OC2
18
E.OC3
32
E.OV1
33
E.OV2
34
E.OV3
48
E.THT
49
E.THM
64
E.FIN
81
E.UVT
Refer to page 77
998, IPM
53
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Description
0 : Light

63 : Dark
Pr.997
Fault
Fault
setting
82
E.ILF
178
E.RET
96
E.OLT
192
E.CPU
97
E.SOT
196
E.CDO
112
E.BE
197
E.IOH
128
E.GF
199
E.AIE
129
E.LF
201
E.SAF
144
E.OHT
208
145
E.PTC
230
E.PID
176
E.PE
245
177
E.PUE
999, AUTO
Automatic parameter setting
Pr.999 Automatic parameter setting
Parameter settings are changed as a batch. Those include
communication parameter settings for the Mitsubishi human
machine interface (GOT) connection, rated frequency settings
of 50Hz/60Hz.
Multiple parameters are changed automatically. Users do not
have to consider each parameter number. (Parameter setting
mode)
Pr.999
setting
9999
(initial
No action
value)
Automatically sets the
communication parameters for the
10
GOT connection with a PU
connector
50Hz
20
rated
frequency
60Hz
21
rated
frequency
 The read value is always "9999".
CL, ALLC, Er.CL, CH
Parameter clear, Initial value change list
Pr.CL Parameter clear
Er.CL Fault history clear
E.OS
Set "1" in Pr.CL Parameter clear to initialize all parameters.
(Calibration parameters are not cleared.) 
E.5
Set "1" in ALLC All parameter clear to initialize all parameters. 
Set "1" in Er.CL Fault history clear to clear alarm history.
Using Pr.CH Initial value change list, only the parameters changed
from the initial value can be displayed.
 Parameters are not cleared when "1" is set in Pr.77 Parameter write
selection.
AUTO Automatic parameter setting
Operation in the
parameter setting
Description
mode (
"AUTO"  "GOT" 
Write "1"
Sets the related
"AUTO"  "F50" 
parameters of the
Write "1"
rated frequency
according to the
power supply
frequency
ALLC All parameter clear
Pr.CH Initial value change list
)