Assembling the glass door:
Assemble the door (including the glass) by hooking it in at the top, and then
screwing it into place at the bottom left and right. Remember to wear work gloves !
Check whether the door's sealing cord fi ts snugly on the appliance!
12
Checking the appliance after installation:
Having installed the appliance the installer must check the following:
a.
Full functioning of the appliance. Please consult the "Instructions for use &
maintenance manual" supplied separately with the appliance.
b.
The fl ue gas outlet. 10 Minutes after initial use of the appliance there must
be no fl ue gas escape. (See
c.
Combustion air supply. The combustion air supply opening in the space
where the appliance is positioned must equate to the minimal size as outlined
in Chapter 8.
d.
The fi re's visual fl ame picture. Upon ignition you will see short blue/yellow
fl ames. These fl ames will gradually lengthen and become yellower. Once all
the fl ames are yellow the appliance has reached the right temperature.
The appliance is now ready for use.
Attention: Spillage of fl ue gases into the room may not occur !
Check if there is spillage of fl ue gases, after installing the appliance,
and after the yearly maintenance.
• Close all windows and doors in the room
• Check if all ventilation openings according the building regulations
are open
• Ignite the fi re and let the appliance run on maximum position for
10 minutes
• Position a lighted smoke match just in front of the draught diverter
opening. This opening is just above the glass door, in the middle.
The smoke must be drawn fully into the opening.
• During the test NO SMOKE may enter into the room !
• If there is any doubt: Let the appliance run for another 5 minutes
and do the test again.
• Run all extractor fans ,air conditioning ,or air recirculation systems
in this and any adjoining rooms, on full, prior to performing the
spillage test .
When spillage of fl ue gases occurs during one of the tests, dis-
connect the appliance immediately and ask your dealer for advice.