Info Level - Unigas G335A Installation Manual

Table of Contents

Advertisement

PART III: OPERATION
By means of a proper use of the keys, it is possible to enter the various level parameters, as shown in the following flow chart:
1
1
Basic display
2

Info level

The burner and consequently the LMV2x.. are factory set; the air and fuel curves as set as well.
Info level
To enter the Info level, proceed as follows:
1
in any menu position, press keys + and - at the same time, then the program will start again: the display will show OFF.
2
until the display will show InFo, Press the enter (InFo) key
3
then il will show the first code (167) flashing, on the right side it will show the data entered. By pressing + or - it is possible to scroll
(up or down) the parameter list.
4
If a dot-line is shown on the right, there is no enough room for complete visualisation: press enter again the data will be completely
shown for 1 to 3 seconds. By pressing enter or + and- at the same time, the system will exit the parameter visualisation and go
back to the flashing number.
The Info level shows some basic parameters as:
Para-
Description
meter
167
Cubic meters of fule (resettable)
162
Operating hours (resettable)
163
Device operating hours
164
Burners start-ups (resettable)
166
Total number of start-ups
113
Burner number (i.e. serial number)
5
Example: choose parameter 102 to show the date
the display shows parameter 102 flashing on the left and characters ._._ on the right.
3
Service Level
4
Parameter Level
6
2
3
5
4
5
Automatic return after menu use time-out (parameter 127)
6
Switching to the basic display
Para-
Description
meter
107
Software version
102
Software date
103
Device serial number
104
Customer code
105
Version
143
Free
34

Advertisement

Table of Contents
loading

This manual is also suitable for:

G258aG380aG400a