Adjustment procedure for light oil operation
The light oil flow rate can be adjusted choosing a by-pass nozzle that suits the boiler/utilisation output and setting the delivery and
return pressure values according to the ones quoted on the table below and the diagram on Fig. 20 (as far as reading the pressure
values, see next paragraphs).
FLUIDICS W2, WR2 NOZZLE: REFERENCE DIAGRAM (INDICATIVE ONLY)
FLOW RATE kg/h
DIMENSIONS
Min
40
13
50
16
60
20
70
23
80
26
90
30
100
33
115
38
130
43
145
48
160
53
180
59
200
66
225
74
250
82
275
91
300
99
330
109
360
119
400
132
450
148
500
165
550
181
600
198
650
214
700
231
750
250
800
267
Tab. 1
ATTENTION! To achieve the maximum flow rate close completely the return line.
Max
40
Pressure on return (bar)
50
60
70
80
90
100
115
130
145
160
180
200
225
250
Over 100kg/h
275
300
330
360
400
Over 100kg/h
450
500
550
600
650
700
750
800
- - - - - -- - -
Atomisation angle according to the return pressure
_________
% Flow rate
NOZZLE SUPPLY PRESSURE = 25 bar
37
PART III: OPERATION
Atomisation angle
Pressure on return (psi)
Flow rate