Pressure Taps - Unigas G335A Installation Manual

Table of Contents

Advertisement

PART III: OPERATION
MultiBloc MBE
Regulation VD-R whith PS
Decreasing pressure
Fig. 7
ATTENTION: To set the outlet pressure of the VD-R regulator, act on the adjustment ring nut (Fig. 10)
The position of the indicator in the dial indicates the value of the outlet pressure calculated as a percentage of the
full scale of the PS sensor (Fig. 11)
Outlet
MIN
10%
pressure
4 mbar
10 mbar
PS-10/40
0,4 kPa
1,0 kPa
2 "w.c.
4 "w.c.
20 mbar
50 mbar
PS-50/200
2,0 kPa
5,0 kPa
8 "w.c.
20 "w.c.
MultiBloc MBE

Pressure taps

Fig. 9
Increasing pressure
25%
50%
75%
25 mbar
50 mbar
75 mbar
2,5 kPa
5,0 kPa
7,5 kPa
10 "w.c.
20 "w.c.
30 "w.c.
125 mbar
250 mbar
375 mbar
12,5 kPa
25,0 kPa
37,5 kPa
50 "w.c.
100 "w.c.
150 "w.c.
Setting scale is „Not" linear! Various sensors available.
Output pressure according to sensor's measuring
range.
Adjust the outlet pressure to the value specified by the
burner or equipment manufacturer!
While making outlet pressure adjustments, do not
exceed a value that creates a hazardous condition to the
burner!
MAX
100 mbar
10,0 kPa
40 "w.c.
500 mbar
50,0 kPa
Fig. 8
200 "w.c.
Adjusting output pressure for positive pressure
systems (requires PS-10/40 or PS-50/200):
42
25%
50%
10%
Min.
1, 2, 3, 5
Sealing plug
4
For system accessories
75%
Max.

Advertisement

Table of Contents
loading

This manual is also suitable for:

G258aG380aG400a

Table of Contents