RDZ UC 300 V2 Installation & Technical Manual page 44

Table of Contents

Advertisement

SETTINGS OF THE INTEGRATION PARAMETERS
Home
antc
Description
Settings for Pre-Treatment Battery Adjustment
Pre
S ettings for Post-Treatment Batter y
post
Adjustment
Setting the General Integration Parameters
par
Home
mint
Description
Air Temp. Set in Summer Renewal (°C)
trS
Air Temp. Set in Summer Integration (°C)
tiS
Air Temp. Set in Winter Renewal (°C)
trU
Air Temp. Set in Winter Integration (°C)
tiU
Proportional Term (PID) Servomotor
8ppr
Integral Term (PID) Servomotor
tipr
Dead Band Resistance value
DBpr
Minimum percentage value for mixer
mmih
opening (%)
x2
SET
Menu
Menu
int
x2
tec
Menu
PRe
tre
tie
tri
tii
8ppr
tipr
DBpr
mmih
IMPOSTAZIONI DEI PARAMETRI DI INTEGRAZIONE
x4
Tec
iNt
antc
int
antc
Descrizione
Impostazioni per la Regolazione della
Pre
Batteria di Pre-Trattamento
Impostazioni per la Regolazione della
post
Batteria di Post-Trattamento
Impostazione dei Parametri generali di
par
Integrazione
x4
int
antc
PRe
mint
Descrizione
Set Temp. Aria in Rinnovo Estivo (°C)
Set Temp. Aria in Integrazione Estiva (°C)
Set Temp. Aria in Rinnovo Invernale (°C)
Set Temp. Aria in Integrazione Inver. (°C)
Azione Proporzionale (PID) Servomotore
Azione Integrativa (PID) Servomotore
Valore di Banda Morta Resistenza
Valore percentuale minimo di apertura
miscelatrice (%)
44
Access to
the mask
Accesso alla
maschera
pre
mint
Modify - Modifica
Min Max Def.
0.0
30.0
25.0
0.0
30.0
16.0
0.0
30.0
22.0
0.0
50.0
36.0
0
9999
80
0
999
100
0.1
2.0
0.4
0
15
9