RDZ UC 300 V2 Installation & Technical Manual page 43

Table of Contents

Advertisement

SETTINGS OF THE RECIRCULATION DAMPER S1
Home
antc
Description
Enable the pressure transducer
enmp
Enable the damper test
ents
Default percentage of damper opening
pers
in Recirculation with transducer disabled
Set the proportional action value (PID)
bps1
Set the value of the integrative action (PID)
t1s1
Set the value of the derivative action (PID)
tds1
Set the value of Dead Band
dbs1
SETTINGS OF THE ANTIFREEZE PARAMETERS
Home
antc
Description
Set the Antifreeze Activation Temperature
sET
(° C)
Set the Antifreeze Activation delay (sec.)
dly
Sets the cycle time of the Antifreeze
CYC
function (sec.)
x2
SET
Menu
Menu
s-s1
enmp
ents
pers
bps1
t1s1
tds1
dbs1
x2
SET
Menu
Menu
Ice
set
dly
cyc
IMPOSTAZIONI SERRANDA DI RICIRCOLO S1
x2
Tec
s-s1
antc
s-s1
antc
Descrizione
Abilita il trasduttore di pressione
Abilita il Test della Serranda
Percentuale di default apertura serranda
in Ricircolo con trasduttore disabilitato
I m p o s t a i l v a l o r e d e l l ' a z i o n e
proporzionale (PID)
Imposta il valore dell'azione integrativa
(PID)
Imposta il valore dell'azione derivativa
(PID)
Imposta il valore di Banda Morta (Dead
Band)
IMPOSTAZIONI DEI PARAMETRI ANTIGELO
x3
Tec
ICe
antc
Ice
antc
Descrizione
Imposta la Temperatura di Attivazione
Antigelo (°C)
Imposta il ritardo di Attivazione
Antigelo (sec.)
Imposta la durata del ciclo della
funzione Antigelo (sec.)
43
Modify - Modifica
Min
Max
Def.
NO
SI
SI
NO
SI
NO
0
100
50
0
9999
70
0
9999
400
0
999
300
0
32767
4
Modify - Modifica
Min
Max
Def.
-10.0 +10.0
1.0
0
1800
600
0
1800
300