4.5
TECHNICAL MENU / MENU TECNICO
To enter the Technical Menu, a password must be entered:
(default 11).
After entering the correct password, the relevant menu masks will
be displayed, indicated by the appearance of the
Home
Description
Air Flow Setting
POr
Analog Output Reading
Anrd
Setting of S1 Recirculation Damper
s-s1
Setting of antifreeze parameters
ice
Setting Integration Parameters
int
Setting Defrost Parameters
DEFR
Setting Free-Cooling Parameters
fc
Technical Menu Password Set
spu
Access to the Synoptic Menu
sin
Season Command Selector
UI
Communication Parameter Setting
c0m
Setting Filter Control Parameters
flt
Setting Alarm Parameters
Stal
Siphon Parameter Setting
siPH
Load Default Settings
def
icon.
x2
SET
Menu
por
antc
Per accedere al Menu Tecnico è necessario l'inserimento di
una password (default 11) . Dopo aver inserito la password
corretta, verranno visualizzate le relative maschere del menu
contrassegnate a display dalla comparsa dell'icona
x2
Tec
Menu
antc
Descrizione
Impostazione Portate Aria
POr
Lettura Uscite Analogiche
Anrd
Impostazione Serranda Ricircolo S1
s-s1
Impostazione Parametri Antigelo
ice
Impostazione Parametri Integrazione
int
Impostazione Parametri Sbrinamento
sbri
Impostazione Parametri Free-Cooling
fc
Set Password Menu Tecnico
spu
Accesso al Menu Sinottico
sin
Selettore Comando Stagione
iu
Impostazione Parametri Comunicazione
c0m
Impostazione Parametri Controllo Filtri
flt
Impostazione Parametri Allarme
Stal
Impostazione Parametri Sifone
sif0
Carica Impostazioni default
def
41
pu
pud
pud
0
0
11
Password Entry
Inserimento Password
por
.
Access to
the mask
Accesso alla
maschera