Vega VEGABAR 86 Operating Instructions Manual page 57

Submersible pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 86:
Table of Contents

Advertisement

Applies also to the analogue 4 ... 20 mA current output and refers to the set span.
Thermal change, current output
The thermal change of the current output corresponds to the value F
total deviation (according to DIN 16086)".
Fig. 26: Thermal change, current output
Long-term stability (according to DIN 16086)
Applies to the respective digital signal output (e.g. HART, Profibus PA) as well as to analogue cur-
rent output 4 ... 20 mA under reference conditions. Specifications refer to the set span. Turn down
(TD) is the ratio nominal measuring range/set span.
Long-term stability zero signal and output span
Time pe-
riod
Measuring ranges from
0 ... 0.1 bar
(0 ... 10 kPa)
One year
< 0.05 % x TD
Five years
< 0.1 % x TD
Ten years
< 0.2 % x TD
Long-term stability zero signal and output span - version climate-compensated
Nominal measuring range in bar/
kPa
0 ... 0.4 bar/0 ... 40 kPa
0 ... 1 bar/0 ... 100 kPa
0 ... 2.5 bar/0 ... 250 kPa
0 ... 5 bar/0 ... 500 kPa
0 ... 10 bar/0 ... 1000 kPa
0 ... 25 bar/0 ... 2500 kPa
VEGABAR 86 • 4 ... 20 mA
0,3 %
0,15 %
-40°C
-20°C
-0,15 %
-0,3 %
Measuring cell ø 28 mm
Measuring range
0 ... +0.025 bar/0 ... +2.5 kPa
< 0.1 % x TD
< 0.2 % x TD
< 0.4 % x TD
Nominal meas-
uring range in
psig
0 ... 6 psig
0 ... 15 psig
0 ... 35 psig
0 ... 75 psig
0 ... 150 psig
0 ... 350 psig
< 0.05 %/10 K, max. < 0.15 %, each with -40 ... +80 °C
(-40 ... +176 °F)
40°C
60°C
20°C
Measuring cell ø 28 mm
< (1 % x TD)/year
< (0.25 % x TD)/year
< (0.1 % x TD)/year
11 Supplement
in chapter " Calculation of the
a
80°C
Measuring cell
ø 17.5 mm
< 0.1 % x TD
< 0.2 % x TD
< 0.4 % x TD
Measuring cell
ø 17.5 mm
< (1.5 % x TD)/year
< (0.375 % x TD)/year
< (0.15 % x TD)/year
57