6 Set up with the display and adjustment module
Reset
Copy instrument settings
36
Select the requested simulation variable and set the requested value.
To deactivate the simulation, you have to push the [ESC] key and
confirm the message " Deactivate simulation" with the [OK] key.
Caution:
During simulation, the simulated value is output as 4 ... 20 mA current
value and with instruments 4 ... 20 mA/HART in addition as digital
HART signal. The status message within the context of the asset
management function is " Maintenance".
Note:
Without manual deactivation, the sensor terminates the simulation
automatically after 60 minutes.
6.5.4 Additional adjustments
After a reset, certain parameter adjustments made by the user are
reset.
The following reset functions are available:
Delivery status: Restores the parameter settings at the time of
shipment from the factory, incl. the order-specific settings. Any user-
defined linearisation curve as well as the measured value memory are
deleted.
Basic settings: Resetting of the parameter settings incl. special
parameters to the default values of the respective instrument. Any
user programmable linearization curve as well as the measured value
memory are deleted.
Note:
You can find the default values of the device in chapter " Menu over-
view".
The instrument settings are copied with this function. The following
functions are available:
Read from sensor: Read data from sensor and store into the
display and adjustment module
Write into sensor: Store data from the display and adjustment
module back into the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
All data of the menu " Setup" and " Display"
VEGABAR 86 • 4 ... 20 mA