Vega VEGABAR 86 Operating Instructions Manual page 54

Submersible pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 86:
Table of Contents

Advertisement

11 Supplement
Min./Max. adjustment:
Ʋ Percentage value
Ʋ Pressure value
Zero/Span adjustment:
Ʋ Zero
Ʋ Span
Ʋ Difference between zero and span
Max. permissible Turn Down
Switch-on phase
Start-up time with operating voltage U
Ʋ ≥ 12 V DC
Ʋ < 12 V DC
Starting current (for run-up time)
Output variable
Output signal
Connection technology
Range of the output signal
Signal resolution
Fault signal, current output (adjustable)
Max. output current
Load
Damping (63 % of the input variable),
adjustable
Output variable - Additional current output
For details on the operating voltage see chapter "Voltage supply"
Output signal
Range of the output signal
Signal resolution
Fault signal, current output (adjustable)
Max. output current
Starting current
Load
Damping (63 % of the input variable),
adjustable
Dynamic behaviour output
Dynamic characteristics depending on medium and temperature
54
-10 ... 110 %
-20 ... 120 %
-20 ... +95 %
-120 ... +120 %
max. 120 % of the nominal range
Unlimited (recommended 20 : 1)
B
≤ 9 s
≤ 22 s
≤ 3.6 mA
4 ... 20 mA - passive
Two-wire
3.8 ... 20.5 mA (default setting)
0.3 µA
≤ 3.6 mA, ≥ 21 mA, last measured value
21.5 mA
See load resistance under Power supply
0 ... 999 s
4 ... 20 mA (passive)
3.8 ... 20.5 mA (default setting)
0.3 µA
Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
21.5 mA
≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA
Load resistor, see chapter "Voltage supply"
0 ... 999 s
VEGABAR 86 • 4 ... 20 mA