Vega VEGABAR 86 Operating Instructions Manual page 37

Submersible pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 86:
Table of Contents

Advertisement

Scaling (1)
Scaling (2)
Current output (meas.
variable)
Current output (adjust-
ment)
VEGABAR 86 • 4 ... 20 mA
In the menu " Additional adjustments" the items " Reset, Date/
Time"
The user-programmable linearization curve
The copied data are permanently saved in an EEPROM memory in
the display and adjustment module and remain there even in case of
power failure. From there, they can be written into one or more sen-
sors or kept as backup for a possible electronics exchange.
Note:
Before the data are saved in the sensor, a safety check is carried out
to determine if the data match the sensor. In the process the sensor
type of the source data as well as the target sensor are displayed. If
the data do not match, a fault message is outputted or the function is
blocked. The data are saved only after release.
In menu item " Scaling" you define the scaling variable and the scal-
ing unit for the level value on the display, e.g. volume in l.
In menu item " Scaling (2)" you define the scaling format on the dis-
play and the scaling of the measured level value for 0 % and 100 %.
In menu item " Current output, variable" you specify which measured
variable is output via the current output.
Depending on the selected measured variable, you assign in the
menu item " Current output, adjustment" the measured values that
4 mA (0 %) and 20 mA (100 %) of the current output refer to.
If the measuring cell temperature is selected as measured variable,
then e.g. 0 °C refers to 4 mA and 100 °C to 20 mA.
6 Set up with the display and adjustment module
37