Vega VEGABAR 86 Operating Instructions Manual page 45

Submersible pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 86:
Table of Contents

Advertisement

Code
Text message
F113
Communication error
F260
Error in the calibration
F261
Error in the instrument set-
tings
F264
Installation/Setup error
F265
Measurement function dis-
turbed
Function check
Code
Text message
C700
Simulation active
Out of specification
Code
Text message
S600
Impermissible electronics
temperature
S603
Impermissible operating volt-
age
S605
Impermissible pressure value
VEGABAR 86 • 4 ... 20 mA
Cause
Error in the internal instrument commu-
nication
Error in the calibration carried out in the
factory
Error in the EEPROM
Error during setup
Error when carrying out a reset
Inconsistent settings (e.g.: distance, ad-
justment units with application process
pressure) for selected application
Invalid sensor configuration (e.g.: ap-
plication electronic differential pressure
with connected differential pressure
measuring cell)
Sensor no longer carries out a meas-
urement
Cause
A simulation is active
Cause
Temperature of the electronics in the
non-specified range
Operating voltage below specified
range
Measured process pressure below or
above the adjustment range
9 Diagnostics and servicing
Rectification
Disconnect operating voltage briefly
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Repeat setup
Repeat reset
Modify settings
Modify connected sensor configuration
or application
Carry out a reset
Disconnect operating voltage briefly
Rectification
Finish simulation
Wait for the automatic end after
60 mins.
Rectification
Check ambient temperature
Insulate electronics
Use instrument with higher tempera-
ture range
Check electrical connection
If necessary, increase operating voltage
Check nominal measuring range of the
instrument
If necessary, use an instrument with a
higher measuring range
45