Required Minimum Clearances
®
Building Exterior Unit Opening Requirements
VRP units must be installed on an outside wall. Confined spaces and/or covered areas should be avoided. Units must
be installed no closer than 12" apart when two units are side by side. If three or more units are to operate next to one
another, maintain a minimum of 60" between units or pairs of units (Figure B). If more than two units are sharing a floor
with adjacent, outset units, a minimum distance of 64" must be kept between units (Figure C). Also, a vertical clearance of
60" must be maintained (Figure A) between units. Units installed on the bottom floor must be mounted at least 6" off of the
ground. If two units are facing each other, a minimum distance of 108" must be kept between units (Figure D).
6"
60"
60"
60"
60"
60"
6"
6"
Figure A
Grill Clearance Requirements
Where obstructions are present use the
following guidelines for proper spacing from
the VRP exterior louvered grill. Friedrich
recommends that ALL obstructions are a
minimum of 72" from the exhaust.
For minor obstruction(s) such as lamp poles
or small shrubbery, a clearance of 24" from
the outdoor louver must be maintained.
For major obstructions such as a solid
fence, wall, or other heat rejecting devices
like a condensing unit, a minimum distance
of 72" must be kept.
The the example pictured above is for reference only and does not represent all possible installations. Please contact Friedrich
Air Conditioning for information regarding effects of other installation arrangements.
60" 60"
Figure B
OUTDOOR
CONDENSING
UNIT
32 "
160 "
64"
Figure C
BUILDING
V
POLE
MAJOR OBSTRUCTIONS
108 "
60"
108 "
60"
Figure D
24"
V
SHRUB
FENCE
60"
60"
12"
Figure E
V
8