Unigas G258A Manual Of Installation - Use - Maintenance page 207

Microprocessor controlled gas burners
Hide thumbs Also See for G258A:
Table of Contents

Advertisement

Modbus interface
The tables that follow in this chapter specify the addresses of the readable and writable words that the customer is able to access. The
customer may read and/or write the values using SCADA programs, PLCs, or similar.
The entries under Access have the following meanings:
R/O Read Only, value can only be read
R/W Read/Write, value can be read and written
The number of characters specified under Data type in the case of character strings includes the final \0.
Char10 means that the text is up to 9 characters long. The final \0 character is then added to this
User level
Address Access
Data type
0x0000
R/O
Float
0x0002
R/O
Float
0x0004
R/O
Float
0x0006
R/O
Float
0x0008
R/W
Float
0x000A
R/W
Float
0x1035
R/O
Float
0x1043
R/O
Float
0x1058
R/O
Word
Parameter level
Address Access
Data type
0x3000
R/W
Float
0x3004
R/W
Float
0x3006
R/W
Float
0x300C
R/W
Float
0x3012
R/W
Word
0x3016
R/W
Float
0x3018
R/W
Float
0x301A
R/W
Float
0x301C
R/W
Float
0x301E
R/W
Float
0x3020
R/W
Float
0x3022
R/W
Float
0x3080
R/W
Float
0x3082
R/W
Float
0x3084
R/W
Float
0x3086
R/W
Float
Signal reference
Parameter
X1
Analog input InP1
X2
Analog input InP2
X3
Analog input InP2
WR
Actual setpoint
SP1
Setpoint 1
SP2 (= dSP)
Setpoint 2
---
Analog input InP3 (unfiltered)
---
Actual angular positioning
B1
Burner alarm
Signal reference
Parameter
Pb1
Proportional range 1
dt
Derivative action time
rt
Integral action time
db
Dead band
tt
Controlling element running time
HYS1
Switch-on threshold
HYS2
Switch-off threshold down
HYS3
Switch-off threshold up
HYS4
Switch-on threshold (cooling)
HYS5
Switch-off threshold down (cooling)
HYS6
Switch-off threshold up (cooling)
q
Reaction threshold
At1
Outside temperature 1
Ht2
Boiler temperature 1
At2
Outside temperature 2
Ht2
Boiler temperature 2
14

Advertisement

Table of Contents
loading

This manual is also suitable for:

G335aG380aG400a

Table of Contents