Function indicators
Indicates modes of operation
L1
MAN/AUTO = OFF (automatic control)
ON (manual control)
L2
PRE-HEATING = ON (running)
L3
SELFTUNING = ON (enabled Self)
OFF (disabled Self)
Automatic/Manual adjustment selection
Active only when PV display visualises the process
variable (button pressed for at least 5 sec.)
Press to increment (decrement) any numerical parameter •• Increment (decrement) speed
is proportional to time key stays pressed •• The operation is not cyclic: once the maximum
(minimum) value of a field is reached, the value will not change even if the key remains pressed.
• Outputs
19
Out2
- 5A at 250Vac/30Vdc relay
20
21
- 5A/250Vac relay
Out1
22
6
Out3
- 5A at 250Vac/30vdc relay
5
• Power Supply
Standard:
100...240Vac ± 10%
~
23
Optional:
PWR
11...27Vac/Vdc ± 10%
~
24
Max. power 8VA; 50/60 Hz
• Identification of boards
Power board - Solder side
Select transmitter voltage
N.B. : you can keep the OUT1 relay energized at power-up by
inserting jumper S2 and removing resistance R20.
CPU board - Component side
2
3 • DESCRIPTION OF FACEPLATE
"Inc" and "Dec" key
4 • CONNECTIONS
19
18
20
17
21
16
22
15
23
14
24
13
!
R20
S2
IN/OUT boards
(see appendix)
Select signal at
contact 3
TOP
7
6
8
5
9
4
10
3
11
2
12
1
• Linear input (I)
Linear
-
4
input
in dc
2
current
20mA,
1
+
Ri = 50Ω
• Linear input (V)
Use wires of
Linear input in
2
adequate diameter
-
dc voltage
(min. 1mm
60mV, 1V
PT100, JPT100,
Ri > 1MΩ
5V, 10V
1
Ri > 10KΩ
+
CPU
DISPLAY
Indication of output states
OUT 1 (AL1); OUT 2 (OPEN); OUT 3 (CLOSED)
PV Display: Indication of process variable
Error Indication: LO, HI, Sbr, Err
LO= the value of process variable is < di LO_S
HI= the value of process variable is > di HI_S
Sbr= faulty sensor or input values higher than max. limits
Err= PT100 third wire opened for PT100, PTC or input
values lower than min. limits (i.e.: TC wrong connection)
SV display: Indication of setpoint
Function key
Gives access to the various configuration phases ••
Confirms change of set parameters and browses next or
previous parameter (if Auto/Man key is pressed)
• Inputs
• TC Input
Available thermocouples:
2
J, K, R, S, T
(B, E, N, L, U, G, D, C custom
linearization is available)
- Observe polarities
- For extensions, use the correct
1
compensating cable for the type
of TC used
• Linear input with 3-wire transmitter
Connect at 20mA input
4
+
VT
24V o 15V
3
2
-
+
1
• Input 1 linear with transmitter 2 wires
4
+
VT
24V o 15V
3
2
-
4...20mA
+
1
• Pt100 / PTC / NTC
3
)
2
2
PTC, NTC
1
PTC / NTC
/ Pt100 2 wires
• Device structure
POWER
80379_MHW_600V-T73_06-2012_ENG
-
+
+
S
-
+
-
T
T
Pt100 3 wires