Probe Connection; Power Supply Connection; Output Connection - Unigas G258A Manual Of Installation - Use - Maintenance

Microprocessor controlled gas burners
Hide thumbs Also See for G258A:
Table of Contents

Advertisement

CONNECTIONS DIAGRAM

Probe connection:

PT1000/NTC/PTC: between terminal 3 and 2
PT 100: between terminal 3 and 2 with terminal 1
Passive pressure probe 0/4-20 mA: between terminal 4 ( + ) e 1 ( - )
Note: out4 must be activated ( IO4F must be setted to ON )
Powered pressure probe 0/4-20 mA between terminal 4 (power supply), 2 ( negative) e 1 (positive)
Note: set IO4F to ON to activate Out4

Power supply connection:

Neutral wire: terminal 9
Phase: terminal 10 ( 100...240 Vac )
Close terminals 15-16 to switch to the set point 2

Output connection:

Channel 1: terminal 7 and 8 ( burner on – off )
Channel 2: terminal 11 and 12 (servomotor opens)
Channel 3: terminal 13 and 14 (servomotor closes)
M12927CA