Unigas G258A Manual Of Installation - Use - Maintenance page 173

Microprocessor controlled gas burners
Hide thumbs Also See for G258A:
Table of Contents

Advertisement

Immersion or strap-on sensors
Placing the probes (QAD22.../QAE21.../QAP21.../RCA...)
With pumps on outlet
with 3 ways valves / with 4 ways valves
Panel system / burner control
With pumps on return
with 3 ways valves / with 4 ways valves
Immersion probes installation
Sensors must be installed on the stretch of pipe in which fluid circulates
all the time.
The rigid stem (sensing element doing the measuring) must be inserted
by at least 75mm and must face the direction of flow.
Recommended locations: on a bend or on a straight stretch of pipe but
tilted by 45° and against the flow of fluid.
Protect them to prevent water from infiltrating (dripping gates,
condensation from pipes etc.)
Installing QAD2.. strap-on sensors
Make sure fluid is circulating in the chosen location.
Eliminate insulation and paintwork (including rust inhibitor) on a min.
100mm length of pipe.
Sensors come with straps for pipes up to 100 mm in diameter
Strap-on or immersion sensors?
QAD2.. strap-on sensors
Advantages :
 10 sec. time constant
 Installed with system running (no plumbing work)
 Installation can be changed easily if it proves incorrect.
Limits:
 Suitable for pipe diameters max. 100 mm
 Can be affected by currents of air etc.
QAE2... immersion sensors
Advantages:
 Measure "mean" fluid temperature
 No external influence on measurement such as: currents of air,
nearby pipes etc.
Limits:
 Time constant with sheath: 20 sec.
 Hard to change installation position if it proves incorrect.
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

G335aG380aG400a

Table of Contents