Unigas G258A Manual Of Installation - Use - Maintenance page 200

Microprocessor controlled gas burners
Hide thumbs Also See for G258A:
Table of Contents

Advertisement

ConF > InP >InP2
Input 2 : this input can be used to specify an external setpoint or carry out setpoint shifting
Parameter
FnC2
SEn2
sensor type input 2
ti
OFF2
Sensor offset
SCL2
scale low level
SCH2
scale high level
dF2
digital filter
(bold = factory settings)
ConF > InP >InP3
Input 3: this input is used to acquire the outside temperature
Parameter
SEn3
sensor type input 3sensor
type input 2
OFF3
Sensor offset
dF3
digital filter
(bold = factory settings)
Value
0
1
2
3
1
2
3
4
5
1
-1999..0.. +9999
-1999..0.. +9999
-1999..100.. +9999
0...2...100
Value
0
1
2
-1999..0.. +9999
0...1278...1500
Description
no function
0=
external setpoint (display SPE)
1=
setpoint shifting (display dSP)
2 =
angular positioning feedback
3 =
0 ÷ 20mA
4 ÷ 20mA
0 ÷ 10V
0 ÷ 5V
1 ÷ 5V
0 ÷ 20mA
Correction value measured by the sensor
minimum scale value(for input ohm, mA, V)
maximum scale value(for input ohm, mA, V)
Is used to adapt the digital 2nd order input filter (time in s; 0 s = filter off)
Description
0 =
1 = wire
2 = wire
Correction value measured by the sensor
Is used to adapt the digital 2nd order input filter (time in s; 0 s = filter off)
7