TABLE 5 - SUMMARY OF STANDARD PARAMETER SETTINGS
SENSORS/PROBES
C111
Siemens QAE2120.010
9030
Siemens QAM2120.040 9030
Pt1000 (130°C max.)
5030
Pt1000 (350°C max.)
5030
Pt100 (130°C max.)
0030
Pt100 (350°C max)
0030
Termocouple K
A030
Danfoss/Siemens
F030
4÷20mA p 1,6 bar
Danfoss/Siemens
F030
4÷20mA p 10 bar
Danfoss/Siemens
F030
4÷20mA p 16 bar
Danfoss/Siemens
F030
4÷20mA p 25 bar
Danfoss/Siemens
F030
4÷20mA p 40 bar
Siemens QBE2.. P4
G030
Siemens QBE2.. P10
G030
Siemens QBE2.. P16
G030
Siemens QBE2.. P25
G030
Siemens QBE2.. P40
G030
Signal 0÷10V
G030 to be fixed to be fixed to be fixed to be fixed to be fixed to be fixed to be fixed
Signal 4÷20mA
F030
tt - servocontrol run
12 sec. Servocontrol Berger STA12B.../Siemens SQN30.251/Siemens SQN72.4A4A20
tt - servocontrol run
13 sec. Servocontrol Berger STA13B...
tt - servocontrol run
15 sec. Servocontrol Berger STA15B...
tt - servocontrol run
30 sec.
NOTES
(*) These values are factory set - values must be set during operation at the plant based on the real working temperature/pres-
sure value.
WARNING
With pressure sensors, parameters SP1, SCH, SCL, HYS1, HYS3 must be selected and displayed in kPa (kilo Pascal).
(1bar = 100,000Pa = 100kPa)
9
C113
SCL
SCH
0110
-
-
0110
-
-
0110
-
-
0110
-
-
0110
-
-
0110
-
-
0110
-
-
0100
0
160
0100
0
1000
0100
0
1600
0100
0
2500
0100
0
4000
0100
0
400
0100
0
1000
0100
0
1600
0100
0
2500
0100
0
4000
to be fixed to be fixed to be fixed to be fixed to be fixed to be fixed to be fixed
Servocontrol Siemens SQL33.03/Siemens SQM10/Siemens SQM50/Siemens SQM54/Berger STM30../
Siemens SQM40.265
PARAMETERS TO BE EDITED
SPL
SPH
HYS1 (*)
30
95
-5
0
80
-2,5
30
95
-5
0
350
-5
0
95
-5
0
350
-5
0
1200
-5
0
160
0
0
1000
0
0
1600
0
0
2500
0
0
4000
0
0
400
0
0
1000
0
0
1600
0
0
2500
0
0
4000
0
HYS3 (*) Pb. 1
dt
rt
5
10
80
350
2,5
10
80
350
5
10
80
350
10
10
80
350
5
10
80
350
10
10
80
350
20
10
80
350
20
5
20
80
50
5
20
80
80
5
20
80
125
5
20
80
200
5
20
80
20
5
20
80
50
5
20
80
80
5
20
80
125
5
20
80
200
5
20
80
5
20
80
5
20
80
SP1 (*)
80°C
40°C
80°C
80°C
80°C
80°C
80°C
100kPa
600kPa
600kPa
600kPa
600kPa
200kPa
600kPa
600kPa
600kPa
600kPa
to be fixed
to be fixed