LIMITED ACCESS LEVEL
Proceed as follows to change some parameters that are not visible in standard user mode:
Press the
key for
3 seconds
Param
Description
SEnS
Input type
SP
Set point 1
AL1
AL1 threshold
HAL1
AL1 hysteresis
Pb
Proportional band
ti
Integral time
td
Derivative time
Str.t
Servomotor stroke time
db.S
Servomotor dead band
SPLL
Minimum set point value
SPHL
Maximum set point value
dp
Decimal point position
SP 2
Set point 2
A.SP
Selection of the active set point
To exit the parameter setting procedure press the
M12927CA
Password = 20
Values
Pt1 = RTD Pt100
Pt10 = RTD Pt1000
0.20 = 0..20mA
4.20 = 4..20mA Pressure probe
0.10 = 0..10V
2.10 = 2..10V
crAL= Thermocouple K
SPLL ... SPLH
AL1L... AL1H (E.U.)
1... 9999 (E.U.)
1... 9999 (E.U.)
0 (oFF) ... 9999 (s)
0 (oFF) ... 9999 (s)
5...1000 seconds
0...100%
-1999 ... SPHL
SPLL ... 9999
0... 3
SPLL...SPLH
"SP" ... " nSP"
key (for 3 s) or wait until the timeout expiration (about 30 seconds)
6
Access to parameter:
Increase the displayed value
Decrease the displayed
value
Confirm and go to next
parameter
Default
Depends on the probe
See page 7
60
SP