Split system single phase type
Quick setback
Line no.
HC1
HC2
760
1060
780
1080
Room temp limitation
The "Room temperature limitation" function enables
the heating circuit pump to be deactivated should the
room
temperature
temperature setpoint by more than the adjusted
differential.
The heating circuit pump is activated again as soon
as the room temperature falls to a level below the
current room temperature setpoint.
During the time the "Room temperature limitation"
function is active, no heat request is sent to the
producer.
TRx
Actual value of room temperature
TRw
Room temperature setpoint
SDR
Room switching differential
P
Pump
T
Time
Maintenance Document 1589-3
Programming line
Room temp limitation
Quick setback
exceed
the
current
Quick setback
During quick setback, the heating circuit pump is
deactivated and, in the case of mixing circuits, the
room
mixing valve is fully closed.
When using a room sensor, the function keeps the
heating off until the room temperature drops to the
level of the "Reduced" or "Frost protection" setpoint.
If the room temperature falls to the reduced or frost
level, the heating circuit pump is activated and the
mixing valve released.
Quick setback switches the heating off for a certain
period of time, depending on the outside temperature
and the building time constant.
Duration of quick setback when "Comfort" setpoint
minus "Reduced" setpoint = 2 K (e.g. "Comfort"
setpoint = 20 °C and "Reduced" setpoint = 18 °C)
Composite outside
temperature
15°C
10°C
5°C
0°C
-5°C
-10°C
-15°C
-20°C
Building time constant [h]
5
Duration of quick setback [h]
7.7
3.3
2.1
1.6
1.3
1.0
0.9
0.8
57