Fujitsu WATERSTAGE WS A050DD6 Series Maintenance Document page 24

Table of Contents

Advertisement

Split system single phase type
Clear 24: Pressure sensor error
Hydraulic Unit LED: Green 8 flashes / Red 6 flashes
Outdoor Unit LED: flash
Probable causes:
Connector connection failure.
Pressure Sensor failure.
Main PCB failure.
Check:
1. Check connection of the Pressure Sensor:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
2. Check output voltage of Main PCB :
Check voltage of Main PCB (Measure at Main PCB side connector)
1 pin(Red) - 3 pin(Black) DC5V +/- 5%
WO*A060LDC
If the voltage is not correct, replace Main PCB.
3. Check output voltage of Pressure Sensor
Check voltage of Main PCB (Measure at Main PCB side connector)
2 pin(White) - 3 pIn(Black) Voltage is refer to the following graph.
Voltage [V]
If the voltage is not correct, replace Presure Sensor.
24
OK
WO*A080LDC and WO*A100LDT
PRESSURE
SENSOR
OK
Pressure [MPa]
PRESSURE
SENSOR
Maintenance Document 1589-3