Supplementary Source - Fujitsu WATERSTAGE WS A050DD6 Series Maintenance Document

Table of Contents

Advertisement

Split system single phase type

4.3.9 Supplementary source

A supplementary producer can be operated in
addition to the main producer (heat pump).
Release of the supplementary producer depends on
a number of parameters a detailed description of
which is given on the following pages.
Line no.
Programming line
3692
With DHW charging
Defines the release of the supplementary source for
DHW charging:
Locked
The supplementary source will not be released.
Substitute
The supplementary source is released only if the
main source cannot be put into operation (e.g. in the
event of fault).
Line no.
Programming line
3700
Release below outside temperature
3701
Release under outside temperature
Operation of the supplementary source is released
only when the composite outside temperature lies
above or below the set temperature limit.
This enables the supplementary source to lock in a
selected outside temperature range to ensure
bivalent operation of supplementary source and heat
pump.
Overtemperature protection
Line no.
Programming line
3705
Overrun time
Overrun time of release for the external source: If the
integral indicates another heat deficit before the
overrun time has elapsed, the release remains
activated.
Maintenance Document 1589-3
• Release is effected via release relay QX2
• 2-position control is effected via control relay QX3
• Ux can be used to transmit the supplementary
source a DC 0...10 V signal for the required
temperature/output setpoint
Complement
The supplementary producer is released if the output
of the main producer is not
sufficient.
Instantly
The supplementary source will always be released.
To ensure continuous release of the supplementary
source, setting "---" must be selected on the
respective operating lines.
If both release values are enabled, the outside
temperature must satisfy both criteria, thus ensuring
release of the supplementary source .
If the set overrun time elapses before the common
flow temperature drops below the common flow
temperature setpoint, the release is deactivated also.