Split system single phase type
Clear 14: Expansion valve thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 8 flashes
Outdoor Unit LED: flash
Probable causes:
•
Misconnection.
•
Sensor failure.
•
Main PCB failure.
Check:
1. Check the sensor connection:
See if the connector has been removed
-
See if the connection is correct
-
Check for any damage on the sensor cable.
-
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C)
Resistance (kΩ)
169 130 101 79.1 62.6 40.0 26,3 17,8
Temperature (°C)
Resistance (kΩ)
12,3 8,7
- If the thermistor is faulty, replace it.
3. Check the electronic board voltage:
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
WO*A060LDC
EXP VALVE
PIPE
DISCHARGE PIPE
OUTDOOR TEMP
- If there is no voltage, replace Main PCB.
Maintenance Document 1589-3