21.08
DC current control
Bit
Value
0
1 = Enable DC hold. See section
Note: The DC hold function has no effect if the start signal is switched off.
1
1 = Enable post-magnetization. See section
Note: Post-magnetization is only available when ramping is the selected stop mode (see
parameter
2...15
Reserved
0b000...0b1111
21.09
DC hold speed
0.00...1000.00 rpm
21.10
DC current
reference
0.0...100.0%
21.11
Post magnetization
time
0...3000 s
21.14
Pre-heating input
source
Off
On
DI1
DI2
DI3
DI4
DI5
DI6
Description
Activates/deactivates the DC hold and post-magnetization
functions. See section
Note: DC magnetization causes the motor to heat up. In
applications where long DC magnetization times are required,
externally ventilated motors should be used. If the DC
magnetization period is long, DC magnetization cannot
prevent the motor shaft from rotating if a constant load is
applied to the motor.
DC hold
21.03 Stop
mode).
DC magnetization selection.
Defines the DC hold speed in speed control mode. See
parameter
21.08 DC current
(page 70).
DC hold speed.
Defines the DC hold current in percent of the motor nominal
current. See parameter
DC magnetization
(page 70).
After 100 s post-magnetization time, the maximum
magnetization current is limited to the magnetization current
corresponding to the actual flux reference.
DC hold current.
Defines the length of time for which post-magnetization is
active after stopping the motor. The magnetization current is
defined by parameter
See parameter
21.08 DC current
Post-magnetization time.
Selects the source for controlling pre-heating for the motor.
The status of the pre-heating is shown as bit 2 of
status word
3.
Notes:
• The heating function requires that STO is not triggered.
• The heating function requires that the drive is not faulted.
0. Pre-heating is always deactivated.
1. Pre-heating is always activated when the drive is stopped.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
DC magnetization
(page 70).
(page 70).
Settings
(page 71).
control, and section
21.08 DC current
control, and section
21.10 DC current
reference.
control.
status, bit 0)
status, bit 1)
status, bit 2)
status, bit 3)
status, bit 4)
status, bit 5)
Parameters 213
Def/FbEq16
0b0000
1 = 1
5.00 rp
DC hold
See par.
46.01
30.0
1 = 1
0
1 = 1
Off
06.21 Drive
0
1
2
3
4
5
6