ABB ACS560 Firmware Manual page 254

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

254 Parameters
No.
Name/Value
30.18
Torq lim sel
Torque limit set 1
Torque limit set 2
DI1
DI2
DI3
DI4
DI5
DI6
Reserved
EFB
Other [bit]
Description
Selects a source that switches between two different
predefined minimum torque limit sets.
0 = minimum torque limit defined by
torque limit defined by
30.20
1 = minimum torque limit selected by
torque limit defined by
30.22
The user can define two sets of torque limits, and switch
between the sets using a binary source such as a digital
input.
The first set of limits is defined by parameters
30.20. The second set has selector parameters for both the
minimum (30.21) and maximum (30.22) limits that allows the
use of a selectable analog source (such as an analog input).
30.21
0
AI1
AI2
PID
30.23
Other
30.19
30.22
0
AI1
AI2
PID
30.24
Other
30.20
Note: In addition to the user-defined limits, torque may be
limited for other reasons (such as power limitation). See block
diagram
Torque limitation
0 (minimum torque limit defined by
torque limit defined by
30.20
1 (minimum torque limit selected by
torque limit defined by
30.22
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Only for the DCU profile. DCU control word bit 15 received
through the embedded fieldbus interface.
Source selection (see
Terms and abbreviations
30.19
and maximum
are active
30.21
and maximum
are active
30.19
30.18
1
User-defined
0
minimum torque
limit
30.18
1
User-defined
0
maximum torque
limit
on page
496.
30.19
and maximum
are active).
30.21
and maximum
are active).
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
on page 162). -
Def/FbEq16
Torque limit
set 1
and
0
1
2
3
4
5
6
7
8...10
11