292 Parameters
No.
Name/Value
36.14
PVL DC voltage at
peak
0.00...2000.00 V
36.15
PVL speed at peak
-30000.00...
30000.00 rpm
36.16
PVL reset date
1/1/1980...6/5/2159
36.17
PVL reset time
00:00:00...23:59:59
37

37 User load curve

37.01
ULC output status
word
Bit
Name
0
Under load limit
1
Within load range
2
Overload limit
3
Outside load limit
3...15
Reserved
0b0000...0b1111
37.02
ULC supervision
signal
Not selected
Motor speed %
Motor current %
Motor torque %
Output power % of
motor nominal
Output power % of
drive nominal
Other
37.03
ULC overload
actions
Disabled
Warning
Fault
Description
Voltage in the intermediate DC circuit of the drive at the
moment the peak value was recorded.
DC voltage at peak.
Motor speed at the moment the peak value was recorded.
Motor speed at peak.
The date on which the peak value logger was last reset.
Last reset date of the peak value logger.
The time at which the peak value logger was last reset.
Last reset time of the peak value logger.
Settings for user load curve.
See also section
User Load Curve
Displays the status of the monitored signal.
Description
1 = Signal lower than the underload curve.
1 = Signal between the underload and overload curve.
1 = Signal higher than the overload curve.
1 = Signal lower than the underload curve or higher than the
overload curve.
Status of the monitored signal.
Selects the signal to be supervised.
No signal selected. ULC disabled.
01.03 Motor speed %
(page 165).
01.08 Motor current % of motor nom
01.10 Motor torque
(page 165).
01.15 Output power % of motor nom
01.16 Output power % of drive nom
Source selection (see
Terms and abbreviations
Selects an action taken if the signal stays over the overload
curve in a sector for a defined time.
No warnings or fault generated.
The drive generates an
signal has been continuously over the overload curve for a
time defined by parameter
The drive generates a
8002 ULC overload fault
has been continuously over the overload curve for a time
defined by parameter
37.41 ULC overload
(page 49).
(page 165).
(page 166).
(page 166).
A8BE ULC overload warning
37.41 ULC overload
timer.
Def/FbEq16
0.00 V
10 = 1 V
0.00 rpm
See par.
46.01
1/1/1980
-
00:00:00
-
0b0000
1 = 1
Motor
torque %
0
1
2
3
4
5
on page 162). -
Disabled
0
if the
1
timer.
if the signal
2