ACx550 compatibility mode is a way to communicate with an ACx580 drive in such a
way that it looks like an ACx550 drive over Modbus RTU or Modbus TCP. This mode
can be enabled by changing parameter
In the 550 compatibility mode all supported parameters can be read as if the drive
were an ACx550. Some parameters are read only and do not support writes. See the
table below to see which parameters support writes.
ACx550
Name
parameter
01.01
SPEED & DIR
01.02
SPEED
01.03
OUTPUT FREQ
01.04
CURRENT
01.05
TORQUE
01.06
POWER
01.07
DC BUS VOLTAGE
01.09
OUTPUT VOLTAGE
01.10
DRIVE TEMP
01.14
RUN TIME
01.15
KWH COUNTER
01.18
DI 1-3 STATUS
01.19
DI 4-6 STATUS
01.20
AI 1
01.21
AI 2
01.22
RO 1-3 STATUS
01.24
AO 1
01.25
AO 2
01.28
PID 1 SETPNT
01.29
PID 2 SETPNT
01.30
PID 1 FBK
01.31
PID 2 FBK
01.32
PID 1 DEVIATION
01.33
PID 2 DEVIATION
96.78 550 compatibility mode
Read/Write
ACx550
parameter
Read only
01.34
Read only
01.35
Read only
01.36
Read only
01.41
Read only
01.45
Read only
03.01
Read only
03.02
Read only
03.03
Read only
03.04
Read only
03.05
Read only
03.06
Read only
03.07
Read only
03.08
Read only
03.09
Read only
04.01
Read only
04.12
Read only
04.13
Read only
Read only
Read only
Read only
Read only
Read only
Read only
to Enable.
Name
COMM RO WORD
COMM VALUE 1
COMM VALUE 2
MWH COUNTER
MOTOR TEMP
FB CMD WORD 1
FB CMD WORD 2
FB STS WORD 1
FB STS WORD 2
FAULT WORD 1
FAULT WORD 2
FAULT WORD 3
ALARM WORD 1
ALARM WORD 2
LAST FAULT
PREVIOUS FAULT 1
PREVIOUS FAULT 2
Read/Write
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only